Reference price :
Contact us
  • Series
    DS250E
  • Model
    DS250E-300
  • Brand / Made in
    CITEL / FRANCE
  • Type 1 + 2 unipolar surge protector
  • Iimp: 25 kA on 10/350µs impulse
  • Imax: 140 kA on 8/20µs impulse
  • Internal disconnections, status indicators
  • Remote signaling
  • IEC 61643-11, EN 61643-11 and UL1449 ed.4 compliance

The DS250E is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation. They are used to protect biphase, 3-phase or 3-phase + neutral networks in common mode or in common and differential mode. The 'Multi-Varistor' technology used allows the best possible behavior for the LV network (no follow-on current). The DS250E is mounted on a DIN Rail and has a double connection for the active conductor, which allows an optimized connection to the network.

Electrical Characteristics

  • SPD type (following IEC tests): 1+2
  • Network: 230/400 V
  • Nominal line voltage Un: 230 V
  • Max. AC operating voltage Uc: 330 Vac
  • Max. load current(if series connection) IL: 100 A
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec (Without disconnection) UT: 335 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn (Without disconnection or with safety disconnection) UT: 440 Vac disconnection
  • Residual Current Ipe: < 2 mA
  • Operating current Continious current at Uc Ic: < 2 mA
  • Follow current If: None
  • Nominal discharge current (15 x 8/20 µs impulses) In: 70 kA
  • Max. discharge current (max. withstand @ 8/20 µs by pole) Imax: 140 kA
  • Impulse current by pole (max. withstand 10/350µs by pole) Iimp: 25 kA
  • Specific energy by pole (max. withstand 10/350 µs) W/R: 156 kJ/ohm
  • Connection mode(s): L/N or L/PE
  • Protection mode(s): Common or Differential Mode
  • Protection level @ In (8/20µs)) Up: 2.5 kV
  • Admissible short-circuit current Isccr: 50 000 A
  • Internal short circuit protection: No
  • Internal Thermal protection: Yes 

Mechanical Characteristics

  • Technology: MOV
  • Connection to Network: By screw terminals: 6-35mm² / by bus
  • Format: 1-pole modular box assembled
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 3 mechanical indicators
  • Remote signaling of disconnection: Output on changeover contact
  • Dimensions: See diagram

Disconnectors

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: Fuses Type gG - 315 A

Standards

  • Standards compliance: IEC 61643-11 / EN 61643-11 / Ul 1449
  • Certification: EAC

INSTALLATION

DS250E-300 Type 1+2 AC surge protector - 1 pole is connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.

Further information can be found in IEC 61643-12 standard (selection and application principles for low voltage SPD).

  • Combine two DS250E-300 to get DS252E-300 used for AC 230 V single phase network, TN system
  • Combine DS250E-300 with DS100EG-600 to get DS252E-300/G used for AC 230 V single phase network, TT-TN systemm
  • Combine three DS250E-300 to get DS253E-300 used for AC 230/400V 3-phase network, TNC system
  • Combine four DS250E-300 to get DS254E-300 used for AC 230/400V 3-phase+N network, TNS system
  • Combine three DS250E-300 with DS100EG-600 to get DS254E-300/G used for AC 230/400V 3-phase+N network, TT-TNS system

 

closet