  • Series
    DACN1
  • Model
    DACN1-35VGS-40-440
  • Brand / Made in
    CITEL / FRANCE
  • Type 1+2+3 3-Phase+N AC surge protector
  • Max. AC operating voltage: 440 Vac
  • VG Technology
  • Max. discharge current: 70 kA
  • Iimp: 35 kA on 10/350µs impulse
  • No leakage current
  • Unpluggable module for each phase
  • Remote signaling
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 complied

DACN1-35VGS-40-440

The DACN1-35VG is an extreme duty Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod. Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime.

sơ đồ kết nối với mạng điện 3 pha

Electrical Characteristics

  • SPD type: 1+2+3
  • Max. AC operating voltage Uc: 440 Vac
  • Max. load current IL: 100 A
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec (Without disconnection) UT: 580 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn (Without disconnection or with safety disconnection) UT: 770 Vac disconnection
  • Residual Current (Leakage current to Ground) Ipe: None
  • Follow current If: None
  • Nominal discharge current (15 x 8/20 µs impulses) In: 35 kA
  • Max. discharge current (max. withstand @ 8/20 µs by pole) Imax: 70 kA
  • Impulse current by pole (max. withstand 10/350µs by pole) Iimp: 35 kA
  • Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50µs - 8/20µs Uoc: 6 kV
  • Specific energy by pole max. withstand 10/350 µs W/R: 306 kJ/ohm
  • Protection level @ In (8/20µs) and @ 6 kV (1,2/50 µs) Up: 1.8 kV 
  • Admissible short-circuit current Isccr: 50000 A

Mechanical Characteristics

  • Technology: VG
  • SPD configuration: 3-phase+Neutral
  • Connection to Network: By screw terminals: 2.5-25mm² (35mm² rigid)
  • Format: 1-pole modular box assembled
  • Plugable: None
  • Mounting: Symmetrical rail 35 mm (EN60715)
  • Housing material: Thermoplastic UL94-V0
  • Operating temperature: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 1 mechanical indicator by pole - Red/Green
  • Wiring for remote signaling: 1.5 mm² max.
  • Max. Voltage/Current for remote signaling: 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
  • Remote signaling of disconnection: Output on changeover contact

Disconnectors

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: Fuses Type gG - 315 A

Standards

  • Standards compliance: IEC 61643-11 / EN 61643-11
  • Certification: EAC

INSTALLATION

DACN1-35VGS-40-440 Type 1+2+3 AC surge protector - 4 pole is connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. 
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.