    DS70R
  • Model
    DS71R-230
  • Brand / Made in
    CITEL / FRANCE
  • Type 2 AC surge protector 1-pole
  • Max. AC operating voltage: 255 Vac
  • Max. discharge current by pole: 70 kA
  • Technology: MOV
  • Protection mode(s): L/PE or N/PE
  • Remote signaling of disconnection: option DS71RS-230 : output on changeover contact
  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449
  • Certification: CSA /EAC/UL

DS70R type 2 AC surge protector

They are used mainly for primary protection of single and three-phase networks at the main electrical panel. They provide common-mode or differential-mode protection and are available in one-phase, single-phase, 3-phase and 3-phase+Neutral. This SPD is based on association of high energy varistors equipped with thermal disconnector and failure indicator, to comply with standards. The DS70R surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks. Each pole of the SPD is connected between Line(s) and PE and Neutral and PE.

Version with a remote signaling for disconnection indication is also available (DS7*RS). 

The DS70R is available for the main values of AC voltages. The DS70R is DIN rail compatible and is built with a plug-in module (DSM70R-xxx) and a fixed base, which allows an easy and fast maintenance.

DS7xR-230 series:
  • DS71R-230: 230VAC surge protector - 1 pole used for 1 line: L or N
  • Combine two DS71R-230 to get DS72R-230 used for 230VAC single phase network (L+N), AC system: TN, protection mode: L/PE + N/PE 
  • Combine four DS71R-230 to get DS74R-230 used for 230/400 VAC 3-phase network (3L+N), AC system: TNS, protection mode: L/PE + N/PE
  • Combine three DS71R-230 & one DS71G-600 to get DS74R-230/G used for 230/400 VAC 3-phase network (3L+N), AC system: TT-TNS, protection mode: L/N + N/PE

ELECTRICAL PROPERTIES

  • SPD type: 2
  • Network: 230/400 V 
  • Nominal line voltage Un: 230 Vac
  • Max. AC operating voltage Uc: 255 Vac
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec UT: 335 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn UT: 440 Vac disconnection
  • Residual Current Ipe: < 1 mA
  • Operating current Ic: < 1 mA
  • Follow current If: None
  • Nominal discharge current In: 30 kA
  • Max. discharge current Imax: 70 kA
  • Total Maximum discharge current Imax Total: 70 kA
  • Admissible short-circuit current Isccr: 25 000 A
  • Connection mode(s): L/PE or N/PE
  • Protection mode(s): Common Mode or Differential Mode
  • Protection level Up: 1.4 kV
  • Residuel voltage at 10 kA Up-10kA: 1 kV
  • Residuel voltage at 5 kA Up-5kA: 0.9 kV
  • Internal short circuit protection: No
  • Internal Thermal protection: Yes

MECHANICAL PROPERTIES

  • Technology: MOV
  • SPD configuration: 1-pole
  • Connection to Network: By screw terminals: 2.5-25mm² / by bus
  • Format: Plug-in modular box
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature Tu: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection 
  • Disconnection indicator: 2 mechanical indicator by pole
  • Spare module(s): DSM70R-230
  • Remote signaling of disconnection: option DS71RS-230 : output on changeover contact
  • Dimensions: 1TE 

DISCONNECTORS

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: 100 A max. - Fuses type gG

STANDARDS

  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449
  • Certification: CSA /EAC/UL

INSTALLATION

DS71R-230 Type 2 AC surge protector - 1 pole are connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.

Further information can be found in IEC 61643-12 standard (selection and application principles for low voltage SPD).

 