Reference price :
Contact us
  • Series
    DAC80
  • Model
    DAC80-40-275
  • Brand / Made in
    CITEL / FRANCE
  • Description: Type 2 AC surge protector - Re-inforced - pluggable
  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Certification: KEMA
  • Technology: MOV
  • Remote signaling of disconnection: option DAC80S-40-275 : output on changeover contact
  • Network: 230/400 V 3-phase+N
  • AC system: TNS
  • Max. AC operating voltage: 275 Vac
  • Residual Current: < 1 mA
  • Max. discharge current: 80 kA
  • Admissible short-circuit current: 50 000 A

The new DAC80 range

Is defined by its high Imax parameter of 80 kA. Classified in Type 2, the products of this range are intended to be installed inside the main electrical panel.

Its Imax setting of 80 kA makes the DAC80 recommended for installations located in areas susceptible to very strong lightning strikes. Thanks to its very high discharge capacity, this range will have a longer service life than conventional AC surge protection of Type 2 with Imax @ 40 kA.

The electrical diagram of the DAC80 series consists of a block of two high-energy varistors combined with a single thermal disconnect system. CITEL is the only manufacturer to offer a complete range of products reaching such a high Imax.

The products comply with EN 61643-11, IEC 61643-11 and UL1449 ed.5.

 

ELECTRICAL PROPERTIES

  • SPD type: 2
  • Network: 230/400 V 3-phase+N
  • AC system: TNS
  • Max. AC operating voltage Uc: 275 Vac
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec UT: 335 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn UT: 440 Vac disconnection
  • Residual Current Ipe: < 1 mA
  • Follow current If: None
  • Nominal discharge current In: 40 kA
  • Max. discharge current Imax: 80 kA
  • Protection mode(s): L/PE and N/PE
  • Protection level N/PE Up N/PE: 1.6 kV
  • Protection level L/PE Up L/PE: 1.6 kV
  • Admissible short-circuit current Isccr: 50 000 A

MECHANICAL PROPERTIES

  • Technology: MOV
  • Connection to Network: By screw terminals: 2.5-25mm² (35mm² rigid)
  • Format: Plug-in modular box
  • Plugable: Yes
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature Tu: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 1 mechanical indicator by pole - Red/Green
  • Spare module(s): MDAC80-275
  • Remote signaling of disconnection: option DAC80S-40-275 : output on changeover contact
  • Dimensions: See diagram - 4TE (EN43880)
  • Weight: 0.455 kg

NORMS

  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Certification: KEMA

DECONNECTOR

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: Fuses Type gG - 125 A

INSTALLATION

DAC80-40-275 Type 2 AC surge protector - 3-phase+N are connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.

Further information can be found in IEC 61643-12 standard (selection and application principles for low voltage SPD).

 