  • Brand / Made in
    CITEL / FRANCE
  • Din rail plug-in surge protector
  • 2-pair
  • Un: 12 V
  • Shield wire protection
  • Plug-out without line cut-off
  • IEC 61643-21 compliance
  • UL497A
DLA protect I&C, telecommunication equipment and data technology systems from lightning effects and surges. Designed for DIN rail mounting, these surge protectors can be used for all applications with voltages from 6 V to max. 170 V and transmission rates up to 10 Mbit/s and protect one (DLA) to two (DLA2) pairs with a plug-in protection module. The electrical circuit of the DLA consists of a combination of high-performance gas discharge tubes and fast-switching diodes for high discharge capacity and fast response behaviour. The shield connection is additionally earthed via a gas discharge tube. The earthing connection is conveniently made via the top-hat rail. When the plug-in module is unplugged, the transmission signal is not interrupted. Special versions: DLAH are protective devices for applications with higher current values, operating current for connected operating devices up to 2.4 A. DLAW is a version which interrupts the signal transmission when the protection module is pulled out. D3 types aim to realize fine protection and D2 types is specific for floating applicaiton.

ELECTRICAL PROPERTIES

  • Network: RS232, RS485
  • Nominal line voltage Un: 12 V
  • Max. DC operating voltage Uc: 15 Vdc
  • Max. frequency    f max.: > 3 MHz
  • Max. load current IL: 300 mA
  • Max. discharge current Imax: 20 kA
  • Line inductance: No
  • Protection level Up: 30 V (L/L), 20 V (L/PE)
  • Impulse current    Iimp: 5 kA
  • Nominal discharge current In: 5 kA

MECHANICAL PROPERTIES

  • SPD configuration: 2-pair+shielded
  • Connection to Network: By screw terminal: cross section 0.4-1.5mm²
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Protection rating: IP20
  • Failsafe mode: Short-circuit
  • Spare module(s): DLA2M-12D3
  • Dimensions: See diagram

NORMS

  • Standards compliance: IEC 61643-21 / EN 61643-21 / UL497A


 

Installation

  • DLA2-12D3 surge protectors are connected in serial on the network. 
  • The protected equipment must be nearby (protector/equipment distance less than 10 m long). If this rule cannot be followed, «secondary» protection must be installed near the equipment (coordinated surge protection).
  • The total length connection wires to network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. 
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. 
  • Local earthing resistance must be in compliance with the electrical rules.