Installation
DS220-12DC surge protectors are connected in parallel on the DC network and must be equipped with external fuses for short-circuit current protection
- The total length of parallel connection wires to DC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
- Wiring is made by screw connections. On some models, a distribution bus can be used.
- The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
- Local earthing resistance must be in compliance with the electrical rules.