Reference price :
Contact us
  • Series
    DAC1-13
  • Model
    DAC1-13-40-275
  • Brand / Made in
    CITEL / FRANCE
  • Type 1 + 2 AC surge protector
  • Network: 230/400 V 3-phase+N
  • Connection mode(s): L/PE and N/PE
  • Imax : 50 kA (8/20µs impulse)
  • Iimp : 12.5 kA (10/350µs impulse)
  • Pluggable module for each phase
  • Remote signaling (option)
  • EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance

DAC1-13-40-275

Type 1+2 AC surge protector - 3-phase+N, 12.5kA / 50kA
 
DAC1-13 range are replacement product for DS13xR
 
The DAC1-13 series are extreme duty Type 1+2 pluggable SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod.
The technology ‘Multi-varistor” allows a very high discharge current capability in small dimensions and the best possible behavior to the AC network (no follow current).
Impulse current by pole (max. withstand 10/350µs by pole): 12.5 kA
Max. discharge current (max. withstand @ 8/20 µs by pole): 50 kA
In the light of their high discharge capability, the DAC1-13 surge protectors are especially compact and are available in multipolar versions to protect single or 3-phase AC networks.
This SPD is DIN rail compatible.
 

DAC1-13 range

  • DAC1-13-10-275 : 1-pole AC surge protector (L or N), Uc 275Vac
  • DAC1-13-20-275 : single-phase AC surge protector (L + N), Uc 275Vac, AC system: TN 
  • DAC1-13-40-275 : 3-phase AC surge protector (L + N), Uc 275Vac, AC system: TNS
  • DAC1-13-31-275 : 3-phase AC surge protector (L + N), Uc 275Vac, AC system: TT-TNS
Electrical Characteristics
  • SPD type (following IEC tests): 1+2
  • Network: 230/400 V 3-phase+N
  • AC system: TNS
  • Nominal line voltage Un: 230 Vac
  • Max. AC operating voltage Uc: 275 Vac
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec (Without disconnection) UT: 335 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn (Without disconnection or with safety disconnection) UT: 440 Vac disconnection
  • Residual Current (Leakage current to Ground) Ipe: < 1mA
  • Follow current If: None
  • Nominal discharge current (15 x 8/20 µs impulses) In: 20 kA
  • Max. discharge current (max. withstand @ 8/20 µs by pole) Imax: 50 kA
  • Total Maximal discharge current max. total withstand @ 8/20 µs Imax Total: 200 kA
  • Impulse current by pole (max. withstand 10/350µs by pole) Iimp: 12.5 kA
  • Total lightning current(max. total withstand @ 10/350µs) Itotal: 50 kA
  • Specific energy by pole max. withstand 10/350 µs W/R: 40 kJ/ohm
  • Connection mode(s): L/PE and N/PE
  • Protection level L/N @ In (8/20µs) Up L/PE: 1.3 kV
  • Protection level N/PE @ In (8/20µs) Up N/PE: 1.3 kV
  • Residual voltage L/N at 5 kA @ 5 kA (8/20µs) Up-5kA: 1 kV
  • Protection level N/PE at 5 kA @ 5 kA (8/20µs) Up-5kA: 1 kV
  • Admissible short-circuit current Isccr: 50 000 A
Mechanical Characteristics
  • Technology: MOV
  • SPD configuration: 3-phase+N
  • Connection to Network: By screw terminals: 2.5-25 mm² (35 mm² rigid)
  • Format: Plug-in modular box
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature Tu: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 1 mechanical indicator by pole - red/ Green
  • Spare module(s) MDAC1-13-275
  • Remote signaling of disconnection:  option DAC1-13S-40-275 : output on changeover contact
  • Dimensions: 4TE (EN43880)
  • Weight 0.667 kg
Disconnectors
  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: SFD1-13S-40 or 125 A min. - 315 A max. - Fuses Type gG
Standards
  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 5ed.
  • Certification: KEMA

INSTALLATION

DAC1-13-40-275 Type 1+2 AC surge protector - 3-phase+N are connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.

Further information can be found in IEC 61643-12 standard (selection and application principles for low voltage SPD).

closet

CART

No products in your cart
Báo Giá Sản Phẩm