Reference price :
Contact us
  • Series
    DAC15C
  • Model
    DAC15CS-20-275
  • Brand / Made in
    CITEL / FRANCE
  • Compact 1-phase Type 2 (or 3) surge protector - 230 V - Pluggable
  • In : 5 kA
  • Imax : 15 kA
  • Commun/Differential mode
  • Pluggable module
  • Remote signaling
  • EN 61643-11, IEC 61643-11 certified
  • UL1449 ed.5 compliance

DAC15CS-20-275

The DAC15C Type 2 or Type 3 Compact plugable surge protectors (SPD) are intended to be connected at the TGBT or divisional panel level. Their compact format allows them to be installed in very small spaces. The DAC15C SPDs are available have a discharge capacity of 15 kA, in single-phase or 3-phase configuration and with various voltages in order to protect any type of networks. Based on varistance technology equipped with disconnector and associated indicator, these SPD ensure maximum protection efficiency, flow capacity and reliability.

ELECTRICAL PROPERTIES

  • SPD type: 2/3
  • Network: 230 V single-phase
  • AC system: TN
  • Nominal line voltage Un: 230 Vac
  • Max. AC operating voltage Uc: 275 Vac
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec UT: 335 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn UT: 440 Vac disconnection
  • Residual Current Ipe: < 1 mA
  • Operating current Ic: 0.5 mA
  • Follow current If: None
  • Nominal discharge current (15 x 8/20 µs impulses) In: 5 kA
  • Max. discharge current (max. withstand @ 8/20 µs by pole) Imax: 15 kA
  • Total Maximum discharge current Imax Total: 30 kA
  • Withstand on Combination waveform IEC 61643-11 (Class III test: 1.2/50µs - 8/20µs) Uoc: 10 kV 
  • Connection mode(s): L/PE and N/PE
  • Protection level N/PE @ In (8/20µs) Up N/PE: 0.9 kV
  • Protection level L/PE @ In (8/20µs) Up L/PE: 1.2 kV
  • Admissible short-circuit current Isccr: 10 000 A  

MECHANICAL PROPERTIES

  • Technology: MOV
  • SPD configuration: single phase
  • Connection to Network: By screw terminals: L/N = 1.5-10mm² (16mm² rigid) or PE = 2.5-25mm² (35mm² rigid)
  • Format: compact plug-in modular box
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature Tu: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 1 mechanical indicator - Red/Green
  • Spare module(s): MDAC15C-20-275
  • Remote signaling of disconnection: output on changeover contact
  • Wiring for remote signaling: 1.5 mm² max
  • Max. Voltage/Current for remote signaling: 250 V / 0.5 A (AC) / 30 V / 3 A (DC)

STANDARDS

  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Certification: KEMA 

DISCONNECTORS

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Back-up protection device: 20 A min. - 125 A max. - Fuses type gG

INSTALLATION

DAC15CS-20-275 Type 2/3 AC surge protector - single-phase are connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.

Further information can be found in IEC 61643-12 standard (selection and application principles for low voltage SPD).

 