• Series
    DS440
  • Model
    DS440-280
  • Brand / Made in
    CITEL / FRANCE
  • Description: Compact 3-phase+N Type 2 surge protector - 230/400 V - Pluggable
  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Certification: EAC
  • Technology: MOV
  • SPD configuration: 3-phase+Neutral
  • Remote signaling of disconnection: Option DS440S-280 : output on changeover contact
  • Network: 230/400 V 3-phase
  • AC system: TN
  • Max. AC operating voltage : 280 Vac
  • Residual Current : < 0.5 mA
  • Max. discharge current : 40 kA
  • Admissible short-circuit current: 10 000 A

DS440-280 - COMPACT 3-PHASE+N TYPE 2 SURGE PROTECTOR - 230/400 V - PLUGGABLE

The DS440 Type 2 surge protectors are compact devices designed to protect 3-phase+N networks at the main switchboard. They provide a common or common/differential mode protection. This SPD is based on high energy varistor equipped with thermal disconnectors and failure indicator to comply with standards. The DS440 is DIN rail compatible and is built with a plug-in module and fixed base, which allows an easy and fast maintenance.

ELECTRICAL PROPERTIES

  • SPD type: 2
  • Network: 230/400 V 3-phase+N
  • AC system: TN
  • Nominal line voltage Un: 230 Vac
  • Max. AC operating voltage Uc: 280 Vac
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec UT: 335 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn UT: 440 Vac disconnection
  • Residual Current Ipe: < 0.5 mA
  • Follow current If: None
  • Nominal discharge current In: 20 kA
  • Max. discharge current Imax: 40 kA
  • Protection mode(s): L/PE and N/PE
  • Protection mode(s): Common mode/Differential mode
  • Protection level CM/DM Up mc/md: 1.3 kV
  • Admissible short-circuit current Isccr: 10 000 A  

MECHANICAL PROPERTIES

  • Technology: MOV
  • SPD configuration: 3-phase+Neutral
  • Connection to Network: By screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE)
  • Format: Plug-in modular box
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature Tu: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 4 mechanical indicator 
  • Spare module(s): DSM440-280
  • Remote signaling of disconnection: option DS440S-280 : output on changeover contact
  • Dimensions: See diagram 
  • Weight: 0.235 kg

NORMS

  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Certification: EAC

DECONNECTOR

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: 50 A min. - 125 A max. - Fuses Type gG

INSTALLATION

DS440-280 Type 2 AC surge protector - 3-phase+N are connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.

Further information can be found in IEC 61643-12 standard (selection and application principles for low voltage SPD).

 