  • Series
    DACN1
  • Model
    DACN1-25VGS-10-760
  • Brand / Made in
    CITEL / FRANCE
  • Type 1+2+3 AC surge protector - 1 pole
  • Max. AC operating voltage: 760 Vac
  • VG Technology
  • Max. discharge current: 70 kA
  • Iimp: 25 kA on 10/350µs impulse
  • No leakage current
  • Unpluggable module for each phase
  • Remote signaling
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 complied

DACN1-25VGS-10-760

The DACN1-25VG is an extreme duty Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod, and in wind turbines' application, the low-voltage side of transformer and power side of convertor is the typical application. Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime.

DACN1-25VG series:

  • Combine two DACN1-25VGS-10-760 to get DACN1-25VGS-20-760 used for AC single phase network (L+N)
  • Combine three DACN1-25VGS-10-760 to get DACN1-25VGS-30-760 used for AC 3-phase network (3L)
  • Combine four DACN1-25VGS-10-760 to get DACN1-25VGS-40-760 used for AC 3-phase + N network (3L+N)

 

DACN1-25VGS-10-760 - Schematic & Dimensions

Electrical Characteristics

  • SPD type: 1+2+3
  • Network: 400/690 V 
  • Max. AC operating voltage Uc: 760 Vac
  • Max. AC operating voltage Uc: 760 Vac
  • Max. load current IL: 100 A
  • Temporary Over Voltage (TOV) Charasteristics - 5 sec (Without disconnection) UT: 1000 Vac withstand
  • Temporary Over Voltage (TOV) Charasteristics - 120 mn (Without disconnection or with safety disconnection) UT: 1325 Vac disconnection
  • Residual Current Ipe: None
  • Follow current If: None
  • Nominal discharge current (15 x 8/20 µs impulses) In: 35 kA
  • Max. discharge current (max. withstand @ 8/20 µs by pole) Imax: 70 kA
  • Impulse current by pole (max. withstand 10/350µs by pole) Iimp: 25 kA
  • Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50µs - 8/20µs Uoc: 6 kV
  • Specific energy by pole max. withstand 10/350 µs W/R: 156 kJ/ohm
  • Protection mode(s): L/PE
  • Protection level @ In (8/20µs) and @ 6 kV (1,2/50 µs) Up: 2.5 kV
  • Protection level L/PE @ In (8/20µs) Up L/PE: 2.5 kV
  • Residual voltage L/PE at 5 kA @ 5 kA (8/20µs) Up-5kA: 1.6 kV
  • Admissible short-circuit current Isccr: 50000 A

Mechanical Characteristics

  • Technology: VG Technology (MOV+GSG)
  • SPD configuration: single phase
  • Connection to Network: By screw terminals: 2.5-25mm² (35mm² rigid)
  • Format: 1-pole modular box assembled
  • Plugable: No
  • Mounting: Symmetrical rail 35 mm (EN60715)
  • Housing material: Thermoplastic UL94-V0
  • Operating temperature: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 1 mechanical indicator by pole - Red/Green
  • Remote signaling of disconnection: Output on changeover contact
  • Wiring for remote signaling: 1.5 mm² max.
  • Max. Voltage/Current for remote signaling: 250 V / 0.5 A (AC) / 30 V / 3 A (DC)

Disconnectors

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type S or delayed
  • Fuses: Fuses Type gG - 315 A

Standards

  • Standards compliance: IEC 61643-11 / EN 61643-11
  • Certification: TUV

INSTALLATION

DACN1-25VGS-10-760 Type 1+2+3 AC surge protector - 1 pole is connected in parallel on the AC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to AC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. 
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • The cross sectional wire must be 6 mm² minimum for Type 2 SPD and 16 mm² for Type 1.
  • Local earthing resistance must be in compliance with the electrical rules.