• Series
    DLAH
  • Model
    DLAH-48D3
  • Brand / Made in
    CITEL / FRANCE
  • 1-pair DIN rail plug-in Data surge protector
  • Network: IDSN, 48 V line
  • Standards compliance: IEC 61643-21 / EN 61643-21 / UL497B
  • Certification: UL Listed
  • Technology: GDT+TVS diode
  • SPD configuration: 1-pair+shielded
  • Max. DC operating voltage: 53 Vdc
  • Max. discharge current : 20 kA
  • Coordination inductor
  • Up to 2.4 A line current
  • Protection level 70 V
  • Cut-off frequency > 1.8 MHz

DLA-48D3

DLAH-48D3 is one of Citel's DIN signal line surge protectors, used exclusively for 48V or ISDN-T0 transmission lines, mounted in series on a pair of signal wires + shield, to protect data transmitting and receiving devices from damage caused by lightning and switching overvoltage.

ELECTRICAL PROPERTIES

  • Network: IDSN, 48 V line
  • Nominal line voltage Un: 48 V
  • Max. DC operating voltage Uc: 53 Vdc
  • Max. frequency f max.: > 1.8 MHz
  • Max. load current IL: 2.4A
  • Max. discharge current Imax: 20 kA
  • Line inductance: 10 µH
  • Protection level Up: 70 V
  • Impulse current Iimp: 5 kA
  • Nominal discharge current In: 5 kA

MECHANICAL PROPERTIES

  • SPD configuration: 1-pair+shielded
  • Connection to Network: By screw terminal: cross section 0.4-1.5mm²
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Protection rating: IP20
  • Failsafe mode: Short-circuit
  • Spare module(s): DLAHM-48D3
  • Dimensions: See diagram

NORMS

  • Standards compliance: IEC 61643-21 / EN 61643-21 / UL497B
  • Certification: UL Listed

Installation

  • DLAH-48D3 surge protectors are connected in serial on the network. 
  • The protected equipment must be nearby (protector/equipment distance less than 10 m long). If this rule cannot be followed, «secondary» protection must be installed near the equipment (coordinated surge protection).
  • The total length connection wires to network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. 
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. 
  • Local earthing resistance must be in compliance with the electrical rules.
closet