Electrical Characteristics
- SPD type 2
- Network DC network: 220 Vdc
- Nominal PV voltage (Uocstc): 220 Vdc
- Max. AC operating voltage (Uc): 210 Vac
- Max. PV operating voltage (Ucpv): 275 Vdc
- Max. DC operating voltage (Uc): 275 Vdc
- Max. load current@25°C (IL): 20 A
- Residual CurrentLeakage current to Ground (Ipe): < 0.1 mA
- PV Permanent Operating current Current consumption at Ucpv (Icpv): < 0.1 mA
- Nominal discharge current15 x 8/20 μs impulses (In): 20 kA
- Max. discharge currentmax. withstand @ 8/20 μs by pole (Imax): 40 kA
- Total Maximum discharge currentmax. total withstand @ 8/20 μs (ImaxTotal): 80 kA
- Current withstand short circuit PV (Iscpv): 1000 A
- Connection mode(s): +/-/PE
- Protection level +/PE (-/PE)@ In (8/20μs) (Up): 900 V
- Admissible short-circuit current (Isccr): 10 000 A
Mechanical Characteristics
- Technology: MOV
- Connection to Network By screw terminals: 1.5-10mm² (actives wires) and 2.5-25mm²(ground)
- Format:Plug-in modular box
- Mounting: Symmetrical rail 35 mm (EN 60715)
- Housing material Thermoplastic:UL94 V-0
- Operating temperature (Tu):-40/+85°C
- Protection rating: IP20
- Failsafe mode: Disconnection from DC network
- Disconnection indicator: 1 mechanical indicator - Red/Green
- Spare module(s): MDDC40C-20-275
- Remote signaling of disconnection: Output on changeover contact
- Wiring for remote signaling: 1.5 mm² max.
- Max. Voltage/Current for remote signaling: 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
- Dimensions: See diagram - 1TE (EN43880)
- Weight: 0.133 kg
Disconnectors
- Thermal disconnector: Internal
- Back-up protection device: 50 A min. - 125 A max. - Fuses Type gG
Standards
- Standards compliance prIEC 61643-41 and UL1449 ed.5