Reference price :
Contact us
  • Series
    DAC50
  • Model
    DAC50S-30-760
  • Brand / Made in
    CITEL / FRANCE
  • Type 2 AC surge protector - 3-pole
  • SPD configuration: 3 phase
  • Max. AC operating voltage : 760 Vac
  • Technology: MOV
  • Residual Current : < 1 mA
  • Max. discharge current : 50 kA
  • Protection level : 2.9 kV
  • Admissible short-circuit current: 50 000 A
  • Remote signaling of disconnection: Output on changeover contact
  • Pluggable module for each phase
  • Standards compliance: IEC 61643-11 / EN 61643-11
  • Certification: OVE / UL

DAC50S-30-760

The pluggable surge protectors Type 2 DAC50, are designed to protect AC powerline at the main switchboard of the installation. These SPDs are based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards and to provide a maximum protection efficiency, a high impulse current capability and an improved reliability. The surge protectors DAC50 are available in multipolar version and in several voltages to protect single or 3-phase networks.

Electrical Characteristics

  • SPD type: IEC 2
  • Network: 400/690 Vac 3-phase
  • AC system: TNC-IT
  • Max. AC operating voltage Uc: 760 Vac
  • Temporary Over Voltage (TOV) Characteristics - 5 sec. Without disconnection UT: 1000 Vac withstand
  • Temporary Over Voltage (TOV) Characteristics - 120 mn Without disconnection or with safety disconnection UT: 1325 Vac disconnection
  • Residual Current Leakage current to Ground Ipe: < 1 mA
  • Follow current If: None
  • Nominal discharge current 15 x 8/20 μs impulses In: 20 kA
  • Max. discharge current max. withstand @ 8/20 μs by pole Imax: 50 kA
  • Total Maximum discharge current max. total withstand @ 8/20 μs Imax Total: 150 kA
  • Protection mode(s): L/PE
  • Protection level L/PE @ In (8/20μs) Up L/PE: 2.9 kV
  • Residual voltage L/PE at 5 kA @ 5 kA (8/20μs) Up-5kA: 2.6 kV
  • Admissible short-circuit current Isccr: 50 000 A

Mechanical Characteristics

  • Technology: MOV
  • SPD configuration: 3-phase
  • Connection to Network By screw terminals: 2.5-25mm²
  • Format: Plug-in modular box
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature Tu: -40/+85°C
  • Protection rating: IP20
  • Failsafe mode: Disconnection from AC network
  • Disconnection indicator: 1 mechanical indicator by pole - Red/Green
  • Spare module(s): MDAC50-760
  • Remote signaling of disconnection: Output on changeover contact
  • Wiring for remote signaling: 1.5 mm² max.
  • Max. Voltage/Current for remote signaling: 250 V / 0.5 A (AC) / 30 V / 3 A (DC)
  • Dimensions: See diagram - 3 TE (EN43880)

Disconnectors

  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type 'S' or delayed
  • Back-up protection device: 50 A min. - 125 A max. - Fuses Type gG

Standards

  • Standards compliance: IEC 61643-11 / EN 61643-11
  • Certification: OVE