  • Protection categories according to the REBT: I, II, III, IV
  • Maximum operating current IL: 63 A
  • Nominal voltage Un: 230 Vac
  • Maximum continuous operating voltage Uc: 275 Vac
  • Nominal frequency: 50-60 Hz
  • Nominal discharge current (8/20 µs) Imax: 100 kA
  • Impulse coordinated current (10/350 µs) Iimp: 100 kA
  • Inductance L: 15 μH
  • Resistance: 3 mΩ

ATLINK 63 Decoupling inductor for protector power supply coordination

Proper protection against transient overvoltages requires good coordination between protectors. ATLINK series inductors produce decoupling between protectors when they are connected in parallel on the same line so that each one acts at the right moment, achieving the double objective of withstanding the lightning current and reducing the overvoltage to an acceptable level for the connected equipment.

  • One ATLINK device is needed for each phase and another for the neutral. When selecting them, the operating current of the line must be taken into account, since this current will flow continuously through the device.
  • Its coordination capability has been tested and certified using lightning wave 10/350 µs according to EN 61643-11.
  • Enables installation of protectors for different stages in the same place, since the inductor substitutes the necessary length of cable for protector coordination.
  • Robust connectors, suitable for all types of connection.
  • ATLINK devices have been tested in official, independent laboratories, verifying that the protectors are correctly coordinated.

 

ELECTRICAL

  • Protection categories according to the REBT: I, II, III, IV
  • Maximum operating current IL: 63 A
  • Nominal voltage Un: 230 Vac
  • Maximum continuous operating voltage Uc: 275 Vac
  • Nominal frequency: 50-60 Hz
  • Nominal discharge current (8/20 µs) Imax: 100 kA
  • Impulse coordinated current (10/350 µs) Iimp: 100 kA
  • Inductance L: 15 μH
  • Resistance: 3 mΩ

ENVIRONMENTAL

  • Working temperature: -40 ºC to +70 ºC
  • Protector location: Indoor
  • Enclosure protection: IP20

CONSTRUCTION

  • Dimensions: 72 x 90 x 80 mm (4 modules DIN 43880) 
  • Fixing: DIN Rail
  • Type of connection: Series (two ports)
  • Enclosure material: Polyamide
  • Insulation resistance: > 10^14 Ω
  • Self-extinguishing enclosure: V-0 Type according to UNE-EN IEC 60707 (UL94)
  • Connections: Min/Max multi-stranded section: 4/35mm2; Min/Max single-stranded section: 1/35mm2

TESTS AND CERTIFICATIONS

  • Certificated tests according to: UNE-EN IEC 61643-11.
  • Complies with requirements of: UL 1449.
  • Relevant standards: UNE 21186, NF C 17-102, IEC 62305.
  • Products compliant with EC requirements.

INSTALLATION

  • ATLINK inductors are to be installed in series with the power supply line, that is, cutting the supply line and connecting the cable ends to the ATLINK input and output connectors. One ATLINK device is needed for each phase.
  • It coordinates the ATSHOCK and/or ATSHIELD protectors with ATSUB and/or ATCOVER protectors when they cannot be separated by a cable at least 10 metres in length.