  • Reference: AT-8201
  • Type 2 AC surge protector, protection neutral-earth
  • Single-pole, size 1 DIN
  • Nominal frecuency: 50 - 60 Hz
  • Nominal discharge current: 20 kA
  • Maximum discharge current: 40 kA
  • Protection level: 1400 V
  • Response time: 25 ns
  • Maximum short-circuit current: 25 kA
  • Certificated tests according to EN IEC 61643-11

ATSUB N protector for power supply lines, protection neutral-earth

Single-pole. Type 2. Imax =40 kA. Up(In) = 1400 V. Up(1,2/50) = 700 V, size 1DIN. Tested and certified as a protector Type 2 according to the standard EN IEC 61643-11. 

Coordinable with protectors of series ATSHOCK, ATSHIELD and ATCOVER.

ATSUB series protectors have been tested in official, independent laboratories, obtaining their characteristics according to relevant standards.

ELECTRICAL

  • Test type according to UNE-EN61643-11: Type 2
  • Protection categories according to the REBT: I, II, III, IV
  • Nominal frecuency f: 50 - 60 Hz
  • Nominal discharge current per pole (8/20 µs wave) In: 20 kA
  • Maximum discharge current per pole (8/20 µs wave) Imax: 40 kA
  • Protection level for 8/20 µs wave at In Up: 1400 V
  • Level protection for 1.2/50 µs wave: 700 V
  • Protection level for 5 kA; 8/20 µs wave: 1000 V
  • Response time tr: 25 ns
  • Backup fuse: 125 A gL/gG
  • Maximum short-circuit current: 25 kA

ENVIRONMENTAL

  • Working temperature: -40 °C to +70 °C
  • Protector location: Indoor
  • Enclosure protection: IP20

CONSTRUCTION

  • Dimensions: L18 mm x H96 mm x W80 mm
  • Weight: 92 gr
  • Number of DIN modules (DIN 43880): 1
  • Fixing: DIN Rail
  • Enclosure material: Polyamide
  • Insulation resistance: > 10^14 Ω
  • Self-extinguishing enclosure: V-0 Type according to EN IEC 60707 (UL94)
  • Type of connection: Parallel (one port)
  • Nr. of poles: 1
  • Warning Warning mechanism: Yellow: protector status ok. Black: Replace.

CONNECTION

  • Minimum multi-stranded section: 4 mm2
  • Maximum multi-stranded section: 35 mm2
  • Minimum single-stranded section: 1 mm2
  • Maximum single-stranded section: 35 mm2
  • Screw: Philips H2
  • Tightening: 3 N·m

TESTS AND CERTIFICATIONS

  • Certificated tests according to EN IEC 61643-11.
  • Complies with requirements of UL 1449.
  • Relevant standards: NF C 17102, UNE 21186, EN IEC 62305.
  • Products compliant with EC requirements.

INSTALLATION

  • ATSUB surge protection devices must be installed in parallel with the low voltage power supply line.
  • When installed as medium protection, they should be separated from the coarse and/or tight protection by at least 10 metres of cable or, if this is not possible, by an ATLINK decoupling
  • inductor, in order to achieve correct coordination between them.
  • Installation should be carried out without power in the line and can only be done by authorized professionals.

SAFETY AND MAINTENANCE

  • Connection to earth is a must. Earthing in the whole installation must be bonded either directly or by a spark gap and resistance should be lower than 10 Ω.
  • If the indications on this datasheet are not fulfilled during use or installation of the protectors, the protection provided by this device could be compromised.