    AT / SPAIN
  • Nominal current: 63 A
  • Type of line: Single-phase
  • Maximum short-circuit current: 6 kA
  • Nominal voltage (L-N) Un: 230 V
  • Maximum overvoltage (L-N) Uc: 400 V
  • Minimum operating voltage (L-N): 80 V
  • Working characteristics for overvoltages: 275 V (8-10 s), 400 V (0,1-0,2 s)
  • Working characteristics for undervoltages: 200 V (0.8 s), 80 V (0.2 s)

IGA TEST PLUS - Protector against permanent overvoltages and undervoltages with integrated miniature circuit breaker.

IGA TEST PLUS series protectors cut off the power supply when they detect a permanent overvoltage or undervoltage, (for example, a fault in the neutral), thus protecting the equipment installed downstream. 

IGA TEST PLUS protectors against permanent overvoltages can be installed together with ATSUB-D transient overvoltage protectors. 

The integrated MCB is available for the most usual nominal currents: 25, 32, 40, 50 and 63 A.

IGA TEST PLUS series protectors have been tested in official, independent laboratories obtaining their characteristics according to applicable standards.

IGA TEST M 63 PLUS - Single-phase protector against permanent overvoltages and undervoltages, with integrated MCB, nominal current 63A. Actuating time 275V -> 8-10s / 400V -> 0,1-0,2s: 80V -> 0,2s / 200V -> 0,8s

IGA TEST M PLUS series:

Name Reference Nominal current (A) Type of line Number of DIN modules
IGA TEST M 25 PLUS AT-9031 25 single-phase 3
IGA TEST M 32 PLUS AT-9032 32 single-phase 3
IGA TEST M 40 PLUS AT-9033 40 single-phase 3
IGA TEST M 50 PLUS AT-9034 50 single-phase 3
IGA TEST M 63 PLUS AT-9035 63 single-phase 3

  

 

  • Name: IGA TEST M 63 PLUS
  • Reference: AT-9035
DIMENSIONS
  • Protector dimensions: 51 x 81 x 65 mm
  • Number of DIN modules (DIN 43880) of the protector: 3
ELECTRICALS
  • Nominal current: 63 A
  • Type of line: Single-phase
  • Maximum short-circuit current: 6 kA
  • Nominal voltage (L-N) Un: 230 V
  • Maximum overvoltage (L-N) Uc: 400 V
  • Minimum operating voltage (L-N): 80 V
  • Working characteristics for overvoltages:
            + Actuation voltage V1 (L-N) Ua: 275 V
            + Actuation time at V1: 8-10 s
            + Actuation voltage V2 (L-N): 400 V
            + Actuation time (V2): 0,1-0,2 s
  • Working characteristics for undervoltages:
            + Actuation voltage V1 (L-N) Ua: 200 V
            + Actuation time at V1: 0.8 s
            + Actuation voltage V2 (L-N): 80 V
            + Actuation time at V2: 0.2 s
CONSTRUCTION
  • Fixing: DIN Rail
  • Insulation resistance: > 10^14 Ω
  • Self-extinguishing enclosure: V-0 Type according to UNE-EN IEC 60707 (UL94)
  • Nr. of poles: 2
ENVIRONMENTAL
  • Working temperature: -5 to +40 °C
  • Protector location: Indoor
  • Enclosure protection: IP20
CONNECTION
  • Protector cables:
            + Min/Max section: 4 / 25 mm2
            + Screw: Philips, H2
            + Tightening: 3 N·m
  • Activation cables (S1, S2):
            + Min/Max section: 1 / 4 mm2
            + Screw: Philips, H1
            + Tightening: 1.2 N·m
TESTS AND CERTIFICATIONS
  • Certificated tests according to the standard: UNE-EN IEC 61643-11
  • UNE-EN IEC 60898
  • UNE-EN 50550 (POP)
  • Relevant standards: UNE 21186, UNE-EN IEC 62305
  • Products compliant with EC requirements.

INSTALLATION

  • They must be installed in series with the low voltage line, with the input at the top of the protector (L, N).
  • The protective coil must be installed between the line and the neutral at the bottom of the protector.

SAFETY AND MAINTENANCE

  • Installation should be carried out without power in the line and can only be done by authorized professionals.

 