Reference price :
Contact us
  • Series
    IGA TEST M PLUS
  • Model
    AT-9033
  • Brand / Made in
    AT / SPAIN
  • Nominal current: 40 A
  • Type of line: Single-phase
  • Maximum short-circuit current: 6 kA
  • Nominal voltage (L-N) Un: 230 V
  • Maximum overvoltage (L-N) Uc: 400 V
  • Minimum operating voltage (L-N): 80 V
  • Working characteristics for overvoltages: 275 V (8-10 s), 400 V (0,1-0,2 s)
  • Working characteristics for undervoltages: 200 V (0.8 s), 80 V (0.2 s)

IGA TEST PLUS - Protector against permanent overvoltages and undervoltages with integrated miniature circuit breaker.

IGA TEST PLUS series protectors cut off the power supply when they detect a permanent overvoltage or undervoltage, (for example, a fault in the neutral), thus protecting the equipment installed downstream. 

IGA TEST PLUS protectors against permanent overvoltages can be installed together with ATSUB-D transient overvoltage protectors. 

The integrated MCB is available for the most usual nominal currents: 25, 32, 40, 50 and 63 A.

IGA TEST PLUS series protectors have been tested in official, independent laboratories obtaining their characteristics according to applicable standards.

IGA TEST M 40 PLUS - Single-phase protector against permanent overvoltages and undervoltages, with integrated MCB, nominal current 40A. Actuating time 275V -> 8-10s / 400V -> 0,1-0,2s: 80V -> 0,2s / 200V -> 0,8s

IGA TEST M PLUS series:

Name Reference Nominal current (A) Type of line Number of DIN modules
IGA TEST M 25 PLUS AT-9031 25 single-phase 3
IGA TEST M 32 PLUS AT-9032 32 single-phase 3
IGA TEST M 40 PLUS AT-9033 40 single-phase 3
IGA TEST M 50 PLUS AT-9034 50 single-phase 3
IGA TEST M 63 PLUS AT-9035 63 single-phase 3

  

 

  • Name: IGA TEST M 40 PLUS
  • Reference: AT-9033
DIMENSIONS
  • Protector dimensions: 51 x 81 x 65 mm
  • Number of DIN modules (DIN 43880) of the protector: 3
ELECTRICALS
  • Nominal current: 40 A
  • Type of line: Single-phase
  • Maximum short-circuit current: 6 kA
  • Nominal voltage (L-N) Un: 230 V
  • Maximum overvoltage (L-N) Uc: 400 V
  • Minimum operating voltage (L-N): 80 V
  • Working characteristics for overvoltages:
            + Actuation voltage V1 (L-N) Ua: 275 V
            + Actuation time at V1: 8-10 s
            + Actuation voltage V2 (L-N): 400 V
            + Actuation time (V2): 0,1-0,2 s
  • Working characteristics for undervoltages:
            + Actuation voltage V1 (L-N) Ua: 200 V
            + Actuation time at V1: 0.8 s
            + Actuation voltage V2 (L-N): 80 V
            + Actuation time at V2: 0.2 s
CONSTRUCTION
  • Fixing: DIN Rail
  • Insulation resistance: > 10^14 Ω
  • Self-extinguishing enclosure: V-0 Type according to UNE-EN IEC 60707 (UL94)
  • Nr. of poles: 2
ENVIRONMENTAL
  • Working temperature: -5 to +40 °C
  • Protector location: Indoor
  • Enclosure protection: IP20
CONNECTION
  • Protector cables:
            + Min/Max section: 4 / 25 mm2
            + Screw: Philips, H2
            + Tightening: 3 N·m
  • Activation cables (S1, S2):
            + Min/Max section: 1 / 4 mm2
            + Screw: Philips, H1
            + Tightening: 1.2 N·m
TESTS AND CERTIFICATIONS
  • Certificated tests according to the standard: UNE-EN IEC 61643-11
  • UNE-EN IEC 60898
  • UNE-EN 50550 (POP)
  • Relevant standards: UNE 21186, UNE-EN IEC 62305
  • Products compliant with EC requirements.

INSTALLATION

  • They must be installed in series with the low voltage line, with the input at the top of the protector (L, N).
  • The protective coil must be installed between the line and the neutral at the bottom of the protector.

SAFETY AND MAINTENANCE

  • Installation should be carried out without power in the line and can only be done by authorized professionals.

 

Other products in the same category

closet

CART

No products in your cart
Báo Giá Sản Phẩm