Reference price :
Contact us
  • Series
    MDS
  • Model
    MDS300S-240Y
  • Brand / Made in
    CITEL / USA
  • Model: MDS300S-240Y
  • AC network: 240/415 Vac Wye 3Ph/N+G
  • Surge Capacity to 300kA 8/20µs Total
  • Lightning Capacity to 22kA 10/350µs Total
  • UL1449 Nominal Discharge Current (In) 20kA (All models)
  • UL1449 Short-circuit Current Rating (SCCR) 200kA (All models)
  • UL96A Master Label Compliant
  • Standard Diagnostics: - % of protection present, audible, remote, test/mute
  • Replaceable Modular Design for SPD and Filter 
  • NEMA 4/12 (Stainless Steel NEMA 4X optional)

MDS series: AC SURGE PROTECTORS AND FILTER HARD-WIRED UNITS AND COMBINER BOXES

MDS series surge protection devices in metal enclosures belong to a complete family of surge protection devices specifically designed to meet the requirements of the North American surge protection standards: USA and Canada. Respectively, the UL1449 ed4 standard and the C22.2 No.269.1–22.2 No.269.5 standards.
These units are based on the use of modular surge protectors like the DS Series. They are equipped with surge protection and an EMI/RFI filtering option.
They are available in all single, dual or three phase configurations and are equipped with various diagnostic options. Housed in a NEMA 4 metal enclosures, these surge protectors are available in various surge capacities (Imax = 300, 600 and 750 kA). Manufactured in accordance with the UL1449 standard, the safe operation is ensured by real-time diagnostics including fault indicators (LEDs), an audible alarm, and remote signal contacts.
 
MDS series NOMENCLATURE
MDSXXXx-yyyz
  • XXX: Imax
  • x:
“   ” Basic: Full Diagnostic, with visual indicator
“S”  Standard: Basic + Internal Fuse
“E”  Enhanced: Standard + Disconnect switch, Surge Counter
  • yyy: Voltage
  • z: Power System Configuration
Example:
MDS300S-240Y
  • 300 = Imax: 300kA
  • S = Standard version
  • 240Y = Voltage: 240/415 V, AC system: Wye 3Ph+N+G

 

Characteristics

  • Model: MDS300S-240Y
  • AC network: 240/415 Vac Wye 3Ph/N+G
  • UL MCOV (L-G) Uc: 275 V
  • TOV Withstand Ut: 335 V
  • UL Nominal Discharge Current In (15 implulses 8/20µs): 20 kA/phase
  • Max. Surge Current (Total) Imax: 300 kA
  • Max. Lightning Current (Total) Iimp (1 implulses 10/350µs): 22 kA
  • Max. Surge Current (Per Phase): 150 kA
  • UL Voltage Protection Rating VPR: 1200 V 
  • UL short-circuit current rating: 200 kA
  • Follow Current If:  none
  • Sine wave tracking: yes
  • Thermal Disconnect: Included
  • Max. Recommended Fuse: 200A, Class J (Basic Only)
  • Dimensions: See Dimensions and Diagram
  • Connection: by screw terminals
  • Remote Signal Indicator: 250Vac Max, 2A
  • Real-time Diagnostics: - % of protection present, audible, remote, test/mute
  • Mounting: Wallmount by screws (not supplied)
  • Operating Temp: -40°C to +85°C (-40°F to +185°F)
  • Enclosure Material: Metal Standard, Stainless Steel option
  • Environmental Rating: NEMA 4, outdoor rated
  • Protection Class: IP56

Standards compliance

  • IEC 61643-1 - INTERNATIONAL: Class I & II
  • EN 61643-11 - EUROPE: Class I & II
  • NF EN 61643-11 - FRANCE: Class I & II
  • UL1449 4th Edition - USA: Type 1
  • UL1449 4th Edition - CANADA: Type 2
  • CSA C22.2 No. 8-M1986: Class 9091 32, Class 9091 92
  • RoHS: Directive 2002/95/EC