Early streamer emission air terminal
DAT CONTROLER® PLUS 15: Early Streamer Emission air terminal. Advance time: 15μs. Protection radius for Protection Level IV and 6 meters height: 52 meters according to NF C 17102 and UNE21186.
GENERAL DESCRIPTION
DAT CONTROLER® PLUS is an Early Streamer Emission (ESE) air terminal based on the electrical characteristics of lightning formation. The air terminal triggers the continuous upward leader before any other object within its radius of protection. This feature is referred to in the regulations as the advance time of an ESE air terminal (ΔT). The earlier the upward leader is triggered, the larger is the distance where the downward leader is intercepted, thus protecting a greater area against lightning (standards limit it to ΔT ≤ 60 μs).
DAT CONTROLER® PLUS CERTIFICATIONS
RADIUS PROTECTION CERTIFICATE AND REGULATION COMPLIANCE
Radius protection certificate for each model and level calculated according to standards UNE 21186:2011, NF C 17-102:2011 and NP 4426:2013.
AENOR PRODUCT CERTIFICATION NO. 058/000005
WITHSTAND CURRENT CERTIFICATE FOR 20 IMPACTS OF 100KA (10/350μs)
Direct application of 20 current impulses (10/350μs) with a peak current higher than 100 kA and specific energy greater than 2.5 MJ/Ω (with positive and negative polarity), according to UNE-EN 60060-1 and IEC 61083-1.
CERTIFICATE OF PERFORMANCE UNDER RAIN
Insulation above 95%
These tests have been performed according to standard UNE-EN 60060-1:2012 in the Electrical Technology lnstitute (ITE).
DAT CONTROLER PLUS ADVANCE TIMES (ΔT)
DAT CONTROLER® PLUS air terminals have passed all the tests according to the standards.
For safety and ease of calculation, the results have been rounded down thus certifying the following advance times (ΔT) in microseconds:
Ref. | Model | ΔT certified |
AT-1515 | DAT CONTROLER PLUS 15 | 15 μs |
AT-1530 | DAT CONTROLER PLUS 30 | 30 μs |
AT-1545 | DAT CONTROLER PLUS 45 | 45 μs |
AT-1560 | DAT CONTROLER PLUS 60 | 60 μs |
DATASHEET
Protection radius (m) | |||||||
Height for protection radius (h) | 2 | 4 | 6 | 8 | 10 | 20 | 60 |
Protection radius (m) for Level I | 13 | 25 | 32 | 33 | 34 | 35 | 35 |
Protection radius (m) for Level II | 15 | 30 | 38 | 39 | 40 | 44 | 45 |
Protection radius (m) for Level III | 18 | 36 | 46 | 47 | 49 | 55 | 60 |
Protection radius (m) for Level IV | 20 | 41 | 52 | 54 | 56 | 63 | 75 |
CERTIFICATIONS AND TESTS