Reference price :
Contact us
  • Series
    DS240-xxDC
  • Model
    DS240-110DC
  • Brand / Made in
    CITEL / FRANCE
  • DC or PV power surge protector
  • 110 Vdc
  • Compact design
  • Imax: 40 kA
  • Pluggable module
  • Remote signaling (option)
  • Very low Up protection level
DS210-DC surge protectors are designed to protect equipment connected to DC (and AC) power supplies from lightning surges. It is based on varistors matched to the network voltage: the varistors have thermal disconnection devices to control any end-of-life. These SPD are DIN rail compatible and is connected in parallel on the line to be protected.

ELECTRICAL PROPERTIES

  • SPD type: 2
  • Network: DC or PV network 110Vdc
  • Nominal DC voltage Un-dc: 110 Vdc
  • Nominal PV voltage Uocstc: 110 Vdc
  • Max. AC operating voltage Uc: 115 Vac
  • Max. PV operating voltage Ucpv: 150 Vdc
  • Max. DC operating voltage Uc: 150 Vdc
  • Max. load current IL: 20 A
  • Residual Current Ipe: < 0.1 mA
  • Operating current Ic: < 0.1 mA
  • PV Permanent Operating current Icpv: < 0.1 mA
  • Follow current If: None
  • Nominal discharge current In: 20 kA
  • Max. discharge current Imax: 40 kA
  • Total Maximum discharge current Imax Total: 80 kA
  • Current withstand short circuit PV Iscpv: 1000 A
  • Connection mode(s): +/-/PE
  • Protection mode(s): Common mode
  • Protection level +/PE (-/PE) Up: 500 V

MECHANICAL PROPERTIES

  • Technology: MOV
  • SPD configuration: 2-poles
  • Connection to Network: By screw terminals: 1.5-10mm² (actives wires) and 2.5-25mm² (ground)
  • Format: Plug-in modular box
  • Mounting: Symmetrical rail 35 mm (EN 60715)
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature: -40/+85°C
  • Protection rating: IP20
  • Outdoor application: No
  • Failsafe mode: Disconnection from DC network
  • Disconnection indicator: 2 mechanical indicators
  • Spare module(s): DSM240-110DC
  • Remote signaling of disconnection: Option DS240S-110DC: output on changeover contact
  • Dimensions: See diagram

NORMS

  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Certification: UL Recognized

DECONNECTOR

  • Thermal disconnector: Internal
  • Fuses: Fuses type gG - 20A

Installation

DS240-110DC surge protectors are connected in parallel on the DC network and must be equipped with external fuses for short-circuit current protection

  • The total length of parallel connection wires to DC network must be lower than 0.5 m in order not to increase the protection level (Up) provided by the SPD.
  • Wiring is made by screw connections. On some models, a distribution bus can be used.
  • The protection wire coming from the SPD must be connected to the bonding bar of the electrical panel. Paralleling the protection wire with phases conductors must be avoided.
  • Local earthing resistance must be in compliance with the electrical rules.