CA 6472 - Earth & Resistivity Tester: 5 tools in 1 with this tester
This tester guarantees reliable measurements:
-
Through the use of traditional rod methods
-
By self-diagnosis at the start of each measurement which indicates the presence of any faults liable to affect the measurements (poor connections or presence of interfering signals)
-
By extensive measurement ranges: 0.001 W to 100 kW
-
By analysing the frequency behaviour of the earthing systems (from 41 Hz to 5 kHz)
The C.A 6472 is eqipped with high-level, expert calculation capabilities:
- For earth coupling measurement, it proposes to carry out the 3 measurements necessary and automatically calculates the coupling coefficient
- For soil resistivity measurement, all you have to do is program the distances used for the measurement and the tester will then calculate r using the Wenner or Schlumberger method.
Other specifications:
-
IP 53 leakproofing
-
Electrical safety: CAT IV 50 V as per IEC 61326-1/ IEC 61010/ IEC 61557-1-4-5
-
Dimensions: 272x250x128 mm
-
Weight 3.2 kg
Technical Datasheet Earth & Resistivity Tester C.A 6472
Model | C.A 6472 |
Reference | P01126504 |
Manufacturer - Origin |
Chauvin Arnoux - France |
Specifications | |
Earth resistance Measurement with 2 clamps | |
Range | 0.01 Ω to 500 Ω |
Resolution | 0.01 Ω to 1 Ω |
Measurement frequency | Auto: 1367 Hz ; Manual: 128 Hz - 1367 Hz - 1611 Hz - 1758 Hz |
Earth resistance 3-pole method | |
Range | 0.01 Ω to 99.9 kΩ |
Resolution | 0.01 Ω to 100 Ω |
Test voltage | 16 V or 32 Vrms rated voltage, selectable by user |
Measurement frequency | 41 Hz to 5078 Hz, automatic or manual |
Test current | Up to 250 mA |
Accuracy | ±2 % of value + 1 count to 128 Hz |
Coupling measurement | Yes |
Earth resistance 4P measurements / 4P + measurements with clamps | |
Range | 0.001 Ω to 99.99 kΩ |
Resolution | 0.001 Ω to 10 Ω |
Test voltage | 16 V or 32 V selectable |
Measurement frequency | 41 Hz to 5078 Hz, automatic or manual |
Test current | Up to 250 mA |
Accuracy | ±2 % of value ±1 count |
Soil resistivity measurement | |
Measurement method | Wenner or Schlumberger method with automatic calculation of results and display in Ω-meter |
Range | (automatic selection) 0.01 to 99.99 kΩ; ρ max. 999 kΩm |
Resolution | 0.01 Ω to 100 Ω |
Test voltage | 16 V or 32 V, selectable |
Measurement frequency | 41 Hz to 512 Hz, selectable |
Earth potential measurement | |
Range | (automatic selection) 0.00 to 65.0 V |
Resolution | 0.01 mV to 10 mV |
Measurement frequency | 41 Hz to 5078 Hz |
Accuracy | ±5 % of value + 1 count at 128 Hz |
External voltage measurement | |
Range | (automatic selection) 0.1 to 65.0 VAC/DC – 15 to 450 Hz |
Accuracy | ±2 % of value + 1 count |
Resistance measurement/ continuity |
|
Type of measurement | 2 wire or 4 wire method, selectable by user |
Range | (automatic selection) 2 wire: 0.01 Ω to 99.9 kΩ – 4 wire: 0.001 Ω to 99.99 kΩ |
Accuracy | ±2 % of value + 2 counts |
Test voltage | 16 VDC (polarity +, - or auto) |
Test current | > 200 mA max. for R < 20 Ω |
Earth resistance measurements with C.A 6474 | |
Range | 0.001 Ω to 99.99 kΩ |
Resolution | 0.001 Ω to 10 Ω |
Test voltage | 16 V or 32 Vrms |
Measurement frequency | 41 Hz to 5078 Hz, automatic or manual |
Test current | Up to 250 mA |
Accuracy | ±5 % of value +1 count |
Data storage | |
Storage capacity | 512 test results |
Communication | Optically-isolated USB |
Other features | |
Power supply | rechargeable NiMH battery |
Battery-charger power supply | External power supply with 18 VDC / 1.9 A output or 12 VDC vehicle power supply |
Electrical safety | 50 V CAT IV, IEC 61010 & IEC 61557 |
Protection | IP53 |
Dimensions / Weight | 272 x 250 x 128 mm / 3.2 kg |