    KIT ATCONTROL/B PT-T PLUS
  • Model
    AT-8777
  • Brand / Made in
    AT / SPAIN
  • Nominal current: 32 A
  • Type of line: three-phase
  • Nominal voltage (L-N) Un: 230 V
  • Maximum overvoltage (L-N) Uc: 400 V
  • Minimum operating voltage (L-N): 80 V
  • Working characteristics for overvoltages: 275 V (3-5 s), 400 V (0,1-0,2 s)
  • Working characteristics for undervoltages: 200 V (3-5 s), 80 V (0.1-0.2 s)
  • Test type according to UNE-EN61643-11: Type 2
  • Maximum discharge current (8/20 µs wave) lmax: 40 kA
  • Protection level at In (1,2/50 µs wave) Up: 1.4 kV

KIT ATCONTROL/B PLUS - Complete kit including self-configurable permanent and transient overvoltage and undervoltage protector, shunt release and circuit breaker.

KIT ATCONTROL/B PLUS series protectors trip the connected shunt release (S1, S2) when they detect a permanent overvoltage. The shunt release causes the circuit breaker to trip, protecting the equipment installed downstream.

The warning system for permanent overvoltages consists of two luminous indicators: green (correct power supply) and red (overvoltage). It has a test button to check that installation has been executed correctly.

KIT ATCONTROL/B PLUS series protectors trip the connected shunt release (S1, S2) when they detect a transient overvoltage, driving the current to earth and reducing the voltage to a level that does not damage the connected equipment.

Tested and certified as type 2 protector in official and independent laboratories, according to standard UNE-EN 61643-11 and GUÍA-BT-23 from the REBT. Suitable for categories I, II, III and IV equipment according to standard ITCBT-23 from the REBT.

It has a thermodynamic control device that disconnects from the electrical network in case of deterioration, and also a warning system for transient overvoltages. When the warning is yellow, the protector is in good condition. If not, replace.

KIT ATCONTROL/B PLUS series protectors have been tested in official, independent laboratories obtaining their characteristics according to applicable standards.

KIT ATCONTROL/B PT-T 32 PLUS - Kit with three-phase protector against permanent and transient overvoltages and undervoltages, shunt release and MCB with nominal current 32A. Actuating time 275V→3-5s/ 400V→0,1-0,2s. 200V→3-5s/ 80V→0,1-0,2s. Imax=40kA.

Name: KIT ATCONTROL/B PT-T 32 PLUS

Reference: AT-8777

DIMENSIONS
  • Protector dimensions: 72 x 90 x 80 mm - 4 DIN modules (DIN 43880)
  • Circuit breaker + shunt release dimensions: 88 x 81 x 65 mm - 5 DIN modules (DIN 43880)
ELECTRICALS
  • Nominal current: 32 A
  • Type of line: Three-phase
  • Maximum short-circuit current: 6 kA
  • Nominal voltage for the shunt release: 110-415 VAC / 110-250 VDC
  • Nominal voltage (L-N) Un: 230 V
  • Maximum overvoltage (L-N) Uc: 400 V
  • Minimum operating voltage(L-N): 80 V
  • Working characteristics for overvoltages: 275 V (3-5 s), 400 V (0,1-0,2 s)
  • Working characteristics for undervoltages: 200 V (3-5 s), 80 V (0.1-0.2 s)

Protection against transient overvoltages

  • Test type according to UNE-EN61643-11: Type 2
  • Protection categories according to the REBT: I, II, III, IV
  • Nominal discharge current (8/20 µs wave) ln: 15 kA
  • Maximum discharge current (8/20 µs wave) lmax: 40 kA
  • Protection level at In (1,2/50 µs wave) Up: 1.4 kV
CONSTRUCTION
  • Type of connection: Parallel (one port)
  • Fixing: DIN Rail
  • Enclosure material: Polyamide
  • Insulation resistance: > 10^14 Ω
  • Self-extinguishing enclosure: V-0 Type according to UNE-EN IEC 60707 (UL94)
  • Nr. of poles: 4
  • Warning for permanent overvoltages: Warning light. Green light: correct mains voltage. Red: overvoltage
  • Warning for transient overvoltages: Warning mechanism. Yellow: protector status ok. Black: Replace
ENVIRONMENTAL
  • Working temperature: -40 to +70 °C
  • Protector location: Indoor
  • Enclosure protection: IP20
CONNECTION
  • Protector cables:
            + Min/Max section: 2.5 / 35 mm2
            + Screw: Philips, H2
            + Tightening: 3 N·m
  • Activation cables (S1, S2):

            + Min/Max section: 1 / 1.5 mm2
            + Screw: DIN 5264, M 2
            + Tightening: 0.25 N·m

  • Cables of Circuit breaker:

            + Min/Max section: 4 / 25 mm2
            + Screw: Philips, H2
            + Tightening: 3 N·m

  • Cables of Shunt release:

            + Min/Max section: 1 / 4 mm2
            + Screw: Philips, H1
            + Tightening: 1.2 N·m

TESTS AND CERTIFICATIONS

  • Certificated tests according to the standard: UNE-EN IEC 61643-11
  • UNE-EN IEC 60898
  • UNE-EN 50550 (POP)
  • Relevant standards: UNE 21186, UNE-EN IEC 62305
  • Products compliant with EC requirements.

INSTALLATION

  • They must be installed in parallel with the low voltage supply line, downstream from the circuit breaker included in the kit.
  • The circuit breaker must be installed in series with the low voltage line.
  • Connect the S1 and S2 terminals, always without voltage, to the shunt release included in the kit.

SAFETY AND MAINTENANCE

  • Installation should be carried out without power in the line and can only be done by authorized professionals.
  • Connection to earth is a must.

 