Tiếng Việt|English
Hotline: +84 902 858 897
ThyAn Company, provider Test & Measurement Devices
CA6460 Earth & Resistivity Tester

CA6460 Earth & Resistivity Tester

Model: CA 6460

Origin: Chauvin-Arnoux / France

Download Catalogue: (Tiếng Việt) (English)

Add to cart:

C.A 6460_Earth expertise

NEW  !

In its rugged, leakproof case, the C.A. 6460 is easy to use, designed specifically for operation in the field. Wherever it is necessary to install an earth connection or characterise an existing earth point, it helps to establish an accurate, fast and reliable diagnosis with optimum comfort and safety.

  • 3-in-1 tester: resistivity, earth, coupling 
  • Measurement range: 0.00 to 2,000W (3 automatic calibres)
  • Change from 4-wire method to 3-wire method thanks to 1 removable captive bar between E and ES
  • 3 fault presence indicators to validate measurement
  • Measurement frequency: 128Hz
  • Easy connection of rods through colour-coded terminals
  • Large backlit digital display with 2,000 counts
  • Power supply: 8x1.5 V batteries for an average battery life, constantly controlled, of 4,500 measurements of 15s each
  • IP53 leakproof case with folding cover and carrying handle
  • Electrical safety: IEC 61010 and IEC 61557
  • Dimensions: 273x247x127 mm - weight: 2.8kg

Technical Datasheet Earth & Resistivity Tester C.A 6460

Model   C.A 6460
Reference   P01126501
Manufacturer - Origin
  Chauvin Arnoux - France
Ground resistance Test method 3P & 4P method
Range 0.00 ... 19.99 Ω / 20.00 ... 199.9 Ω / 200.0 ... 1999 Ω (automatic)
Resolution 10 mΩ / 100 mΩ / 1 Ω
Test current 10 mA / 1 mA / 0.1 mA
Accuracy ±2 % ±1 pt / ±2 % ±1 pt / ±2 % ±3 pt
Measurement frequency 128 Hz
Coupling measurement yes
Ground resistivity Test method Wenner & Schlumberger
Range 0,01 to 99,9 kΩ
Measurement frequency 128 Hz
Response time   between 4 and 8 seconds depending on measurement conditions
Power supply   8 alkaline 1.5 V LR14 batteries or same-size rechargeable NiMH or NiCd storage batteries
Protection   IP53
Conditions for use   -10 °C…+55 °C / 20 %…90 % RH
Dimensions / Weight   273 x 247 x 127 mm / 2.8 kg
EMC   EN 61 000-3, EN 61 000-4
Safety   50 V CAT III, IEC 61010 & IEC 61557

Earth & Resistivity Testers
Products Search
Your Cart
Lightning protection
Measurement Tools
The Essentials 2017