ATCOMPACT T1 50kA AC Surge Protection Panel

ATCOMPACT T1 50kA AC Surge Protection Panel

Model: AT-8150

Origin: AT3W / Spain

Download Catalogue: (English)

Add to cart:

ATCOMPACT T1 50kA- Protection for three phase lines with ATSHOCK 50kA

ATCOMPACT protection boxes are made of several kind of SPD aiming the protection of all lines out from single phase SPD, including the protective fuses against short circuits.

ATCOMPACT Surge Protective Devices are to be installed in parallel with the supply line, without altering at all its way of working under normal conditions. Combinations can be made for protection either in common mode (ground referred) or differential (between line/s and neutral).

Compact box easy to install and with the same advantages as Aplicaciones Tecnologicas SPDs give: robust, quick, reliable and tested according current standards (EN 61643-11) in Official independent laboratories.

Installation ATCOMPACT

ATCOMPACT T1 50kA - Bộ cắt sét nguồn điện 3P-50kA

ATCOMPACT boxes are to be installed in parallel with the Low Voltage supply line, connected to line, neutral and ground. Fuses or circuit breakers must be present upstream. They will be disconnected during the installation for working security. When this ATCOMPACT is installed as middle protection, other protectors must be separated by at least 10 meter cable or, it this is not possible. by decoupling inductors ATLINK, in order to achieve a correct coordination between them.

General nomenclature
- T1 : Three-phase protection type 2
- 50kA: Max. discharge current for single phase

Earthing connection

Earthing in all the installation must be bonded either directly or by a spark gap and resistance should be lower than 10 Ω. If the indications of this datasheet are not fulfilled during the use or installation of the SPDs, the protection assured by this device could be endangered.

ATCOMPACT T1 50kA Technical Datasheet

 Reference  ATCOMPACT T1 50kA
AT-8150
 Protection categories according to REBT  III, IV
 Type of tests according to EN 61643-11 Type 1
 Nominal voltage (Un) 400VAC (L-L) 230VAC (L-GND)
 Maximum working voltage (Uc) 440VAC (L-L) 255VAC (L-GND)
 Nominal frequency  50-60Hz
 Nominal discharge current (wave 8/20μs) (In) 50kA
 Maximum discharge current (8/20μs wave) (Imax)  50kA
 Protection level (1,2/50μs wave) (Up)  4000V
 Response time (tr)  <100ns
 Included fuse  80A gG
 Maximum short-circuit current  100kA
 Working temperature  -400C to +700C
 SPD location  Outdoor
 Type of connection Parallel (one port)
 Number of poles  2
 Dimensions 280 x 448 x 160mm
 Fixing Wall or vertical support
 Enclosure material Autoextinguishing, isolating
 Enclosure protection  IP65 according to IEC 60.529
 Enclosure Double (Class II)
 Fire resistance 650ºC according to IEC 695-2-1
 Impact protection  IK09 according to EN 50.102
 Connections L/N/GND Maximum section 25mm2
 Certificated tests according to: IEC 61643-1, EN 61643-11
 Complies with requirements of: UL 1449
 Relevant standards: UNE 21186, NFC 17102, IEC 62305