Tiếng Việt|English
Hotline: +84 902 858 897
ThyAn Lightning and Surge Protection
APLICEM Ground enhancing cement

APLICEM Ground enhancing cement

Model: AT-034L

Origin: AT3W / Spain

Download Catalogue: (Tiếng Việt) (English)

Add to cart:

Ground enhancing cement

 In high resistivity soils it is necessary to use a specific material to obtain a correct grounding resistance.

APLICEM ground enhancing cement improves grounding effectiveness around any type of earthing rod.

This product is very useful in industries that require a low grounding resistance such as computer installations, radio frequency facilities and substations .

APLICEM enlarges the conductive surface of the earth electrode thus improving its earthing resistance, which decreases drastically. Besides, resistance remains stable regardless of soil moisture.

Therefore, costs are reduced by requiring fewer perforations for an adequate resist

Installation

APLICEM ground enhancing cement is supplied in 11,5kg bags, which contents should be mixed with 5 litters of water. The bag contains 2 parts: the conductive mixtureand the cement.

APLICEM can fill the grounding and improving its resistance for both vertical and horizontal electrodes:

1. Vertical perforations: for filling the ground around the electrode, enlarging its effect and thus improving the earthing resistance.

  • Make the perforation with the required dimensions.
  • Mix with 5 litters of water the cement and the conductive mixture included in the bag.
  • Pour water into the ground to moisten the soil and insert the electrode.
  • Fill the rest of the hole with the mixtures of APLICEM and water, using the electrode for stirring the mixture thus achieving an homogeneous covering.

2. Trenches: for filling the ground around the conductor in order to avoid its corrosion and preserve the obtained resistance.

  • Dig the trench with the required dimensions.
  • Mix with 5 litters of water the cement and the conductive mixture included in the bag.
  • Cover the bottom of the trench with APLICEM, with a thickness of at least 5cm.
  • Place the conductor on the APLICEM layer.
  • Cover the conductor with APLICEM, with a thickness of at least 5cm.
  • Let the mixture harden before filling the rest of the trench.

APLICEM allows rapid and versatile installation. Its volume remains constant and it does not leak out to the soil. It is not corrosive for the conductor, reduces installation costs and can be easily stored during long periods.